  • 2. most variable speed units of that size will do from 3 to 5 tons so it is critical to set the dip switches up right or you will be blasting 5tons of air through your duct 3. is that 15seer a two-speed outdoor unit? if it is then it should run at a lower tonnage in first stage maybe 2-2.5 tons most of the time except on really hot days, so oversizing should not be a problem.